HOW WILL I DEMONSTRATE COMPLIANCE?
TABLE 5-2. METHODS USED TO ESTABLISH OPERATING PARAMETER VALUES
1. Range of values from multiple performance tests or2. +1 inch of H2O column about the average pressure drop measured during three compliant test runs | ||
1. Range of values from multiple performance tests or2. +10 percent about the average velocity pressure measured during three compliant test runs | ||
1. Use 45 dynes/cm or2. Maximum surface tension measured during at least three compliant test runs | ||
1. Use 1 inch foam blanket thickness or2. Minimum foam blanket thickness measured during at least three compliant test runs |
TABLE 5-3. SUMMARY OF ONGOING MONITORING REQUIREMENTS
aAcceptable values for these monitored parameters are established during initial performance testing.
bIf there are no exceedances of the maximum surface tension after 40 hours of operation, then the monitoring frequency can be decreased to once every 8 hours. If there are no exceedances for the next 40 hours, then the frequency can be decreased to once every 40 hours. If an exceedance occurs at any time after that, then the initial monitoring schedule (every 4 hours) must be resumed.
cThe initial schedule must be resumed for every new tank solution.
dIf there are no exceedances of the minimum foam blanket thickness after 40 hours of operation, then the monitoring frequency can be decreased to once every 4 hours. If there are no exceedances for the next 40 hours, then the frequency can be decreased to once every 8 hours. If an exceedance occurs after that, then the initial monitoring schedule (every hour) must be resumed.
There are three components to
demonstrating compliance with the emission limits of this regulation:
INITIAL PERFORMANCE TESTING
What is the purpose of the initial performance test?
There are two reasons to perform
an initial performance test. First, an initial performance test
is necessary to determine if the chromium emissions from the affected
source are the same or lower than the emission limits set for
the source. The emission limits for the different chromium electroplating
tanks and chromium anodizing tanks were listed in Table 4-1.
Second, the initial performance test establishes values or ranges
of values for the air pollution control system operating parameters.
Monitoring and recording these operating parameters during tank
operation will give you an indication of whether or not you are
in compliance with the emission limits.
Summary of testing requirements.
Except for the situations noted
below, you will be required to perform an initial performance
test. This test must be conducted by July 23, 1996 for decorative
chromium electroplaters and by July 24, 1997 for hard chromium
electroplaters and chromium anodizers.
However, sources that meet the
following criteria do not have to perform testing:
A test plan that describes the
proposed initial performance testing program should be developed
prior to testing and may be requested by EPA. The test plan should
describe the process to be tested, the conditions under which
testing is to be conducted, the sampling locations, and the test
methods to be used. Also, you must notify EPA in writing of your
intent to conduct a performance test prior to the test. This notification
is described in Chapter 6 of this guidebook.
The performance test report is
prepared by the test contractor after testing has been conducted.
The test report must contain the information listed in Table 5-1
and must be submitted to EPA as part of the reporting requirements
described in Chapter 6 of this guidebook.
INFORMATION REQUIRED IN INITIAL PERFORMANCE TEST REPORT
Test methods.
EPA Reference Method 306 or 306A, "Determination of
Chromium Emissions from Decorative and Hard Chromium Electroplating
and Anodizing Operations," must be used to determine chromium
emissions from decorative or hard chromium electroplating tanks
or chromium anodizing tanks. Detailed descriptions of these reference
methods are located in Appendix A of part 63 of the
Code of Federal Regulations. The EPA produced a videotape on stack
sampling and monitoring entitled "Construction and Operation
of the EPA Method 306A Sampling Train and Practical Suggestions
for Monitoring of Electroplating and Anodizing Facilities"
that is available to you for a nominal fee through North Carolina
State University, Raleigh, NC by calling (919) 5155875.
The California Air Resources
Board (CARB) Method 425 may also be used to measure chromium
emissions as long as the analytical requirements listed in the
regulation are adhered to. Alternate test methods may also be
used as long as they have been validated using EPA Reference Method 301.
EPA Reference Method 306B,
"Surface Tension Measurement and Recordkeeping for Tanks
Used at Decorative Chromium Electroplating and Anodizing Facilities'"
must be used to determine the surface tension of electroplating
and anodizing baths if you are complying with the surface tension
limit rather than the emission limit.
Monitoring requirements.
During performance testing, applicable air pollution control system
operating parameters must be recorded. These operating parameters
are determined by the air pollution control system you are using
and are listed in Table 52. At the conclusion of testing,
a range of acceptable values or a maximum or minimum value for
these parameters can be established as described below.
For pressure drop measurements,
the range can be established as the range of pressure drops measured
during multiple performance tests, or as plus or minus 1 inch
of water column about the average pressure drop measured during
three compliant test runs (i.e., the source was at or below the
applicable emission limit).
For velocity pressure measurements,
the range can be established as the range of velocity pressures
measured during multiple performance tests, or as plus or minus
10 percent about the average velocity pressure measured during
three compliant test runs.
For surface tension,
a maximum value can be established during performance testing,
or you can forego testing (if you have a decorative chromium electroplating
or a chromium anodizing operation) and accept 45 dynes/cm
as the maximum surface tension value.
For foam blanket thickness,
a minimum foam blanket thickness can be established during performance
testing or the facility can elect to use 1 inch as the minimum
foam blanket thickness.
Applicability of previous
test results.
If you have already conducted a performance test to obtain an
operating permit in your State, the results of the testing can
be used to demonstrate compliance with this regulation only if
each of the following criteria is demonstrated:
If any of these criteria are
not met, then you will have to retest.
ONGOING COMPLIANCE MONITORING
What is the purpose of
ongoing monitoring?
You must continue to monitor the operation of the air pollution
control system to ensure ongoing continuous compliance with the
emission limits. By monitoring and recording the appropriate air
pollution control system parameters and comparing the monitored
values to the range of values, maximum value, or minimum value
established during the performance test, you and the enforcing
agency can determine if you are in compliance with the emission
limits.
How do I know if I am out
of compliance with the emission limits?
Monitored values that fall outside of the range of values established
for pressure drop and velocity pressure, exceed the maximum surface
tension, or fall below the minimum foam blanket thickness indicate
that the tank is out of compliance with the emission limits (i.e.,
excess emissions). Table 53 summarizes the ongoing
monitoring requirements including the monitoring frequency for
the various air pollution control systems.
Can I decrease the monitoring
frequency of monitored values?
The monitoring frequency for pressure drop and velocity pressure
cannot be changed. However, the frequency of monitoring surface
tension and foam blanket thickness can be decreased. Figure 51
is a flowchart showing how the monitoring frequency can be decreased
for a wetting agent, a combination wetting agent/foam blanket-type
fume suppressant, or a foam blanket-type fume suppressant. The
information in Figure 51 is also described in the footnotes
to Table 53.
SPECIAL COMPLIANCE PROVISIONS
The regulation contains special
compliance provisions for determining compliance with the emission
limits under certain circumstances. These special compliance provisions
are applicable in the following situations involving multiple
tanks manifolded to one control system:
In these situations, it would
be very difficult to directly determine compliance with the emission
limits in the regulation. Therefore, section 63.344(e) of the
final regulation provides equations for verifying compliance with
the emission limits in both of these situations.