Safe
Exhaust Recirculation of Manned Spray Booths
How
to keep the cost of pollution control from hurting you
By
Stephen P. Olivier
Vice President of Engineering
Tellkamp Systems, Inc., Santa Fe Springs, CA
|
Painter
in full personnel protective equipment
|
Spray
booths that use robots or automatically reciprocating paint application
equipment are unoccupied during the paint process. For many of these
unmanned spray operations, the time has passed for simple open-faced
spray booths with all of the airflow exhausting out of the back
filter bank plenum. During the last 15 years, spray booth exhaust
has been recirculated in unmanned spray booths in more and more
paint finishing systems. Now, unmanned spray booths are commonly
equipped with recirculation fans, automatically advancing roll-up
filters and ultra-fine return air filters. Recirculation has been
done primarily to reduce the capital equipment and operating costs
when air pollution control equipment for Volatile Organic Compounds
(VOC) is required.
Case
studies have shown examples of cost effective air pollution controls
on recirculated spray booths where the Regenerative Thermal Oxidizer
(RTO) or other control device is one-fourth the size and cost required
without recirculation. When the savings from reducing heated air
make-up costs are factored in, recirculation of spray booth exhaust
can actually pay for the operating or running cost of air pollution
control.
Similar
savings can be obtained by recirculating spray booth exhaust in
manned spray booths such as manual touch-up booths and large-part
spray booths. However, return of air with VOCs to an occupied
space invokes important safety questions. Paint line supervisors
may ask if painters will have to wear respirators or even fresh
air masks. Plant management may wonder if this meets OSHA and fire
safety codes. Here are some suggestions for the practical design
and safe operation of manned spray booths with recirculated exhaust.
|
Recirculating
spray booth system
|
Fire
Safety of spray booths with exhaust recirculation has been
addressed by the National Fire Protection Association (NFPA) in
its national consensus code entitled NFPA 33 2000 Spray
Application Using Flammable or Combustible Materials, NFPA
33 Section 5.5.1 limits recirculation to when the actual VOC concentration
in the return air is kept to less than 25% of the Lower Explosive
Limit (LEL), and an LEL probe is interlocked to the spray operation.
LELs typically run in the 5-10% range for recirculated spray
booths.
Use
of exhaust recirculation does not change the need for fire detection
or fire suppression systems. But if some type of fire detection
or fire suppression system is required, then these systems must
be properly designed for the recirculating spray booth. For example,
additional fire sprinkler heads in the return air plenum may be
needed to effectively protect a recirculating booth.
Painter
Health and Safety requirements are spelled out in OSHAs
respiratory protection standard (29 CFR 1910.134). This standard
requires the use of approved respirators or other Personal Protective
Equipment (PPE) when workers are exposed to actual paint solvent
or VOC concentrations that exceed the OSHA Permissible Exposure
Limit (PEL). PELs for commonly used paint solvents range from
50 ppm for toluene to 500 ppm for acetone. Since paint formulations
contain a mixture of solvents, a Hazard Ratio must be calculated
for each solvent by dividing the actual concentration of the specific
solvent by its respective PEL. If any solvent Hazard Ratio is greater
than 1.0, then a respiratory protection plan with PPE is required.
TABLE 1: Cost Effective Pollution Control Equipment |
|
Standard
Design
|
Recirculated
Booth Design
|
Automatic
Booths (4) |
60,000
cfm
|
16,000
cfm
|
Manual
Booths (4) |
48,000
cfm
|
0
|
Flash-off
Areas |
0
|
3,000
cfm
|
Cure
Oven |
4,000
cfm
|
4,000
cfm
|
Total
Exhaust Flow |
112,000
cfm
|
23,000
cfm
|
Annualized
Operating Cost |
$176,000/yr.
|
$21,600/yr.
|
Annualized
Heated Air Make-up Cost Savings with Reduced Airflow |
-
|
($37,000/yr.)
|
Based
on $0.06/KW, $4.00 per MM Btu, 100 lb/hr. VOC, Heated air make-up
required 60% of the year. |
Keep
in mind that some catalyzed paints have components with a very low
PEL (0.02 ppm for methyl isocyanate). These may require use of PPE
such as supplied breathing air for spray operations even if recirculation
is not used. Also, it is very possible that adding recirculation
to an existing spray booth may increase the actual exposure level
by concentrating the solvents to a level above the permissible PEL.
In this case, PPE must be used.
TABLE
2: Effect of Spray Booth Exhaust Recirculation |
|
No Recirculation
|
Partial
Recirculation
|
Full
Recirculation
|
Spray
Booth Exhaust Rate (cfm) |
10,000
|
3,333
|
2,000
|
Paint
Use (gal./hr.) |
5
|
5
|
5
|
Solvent
Exposure (ppm) |
30
|
90
|
150
|
Solvent
PEL (ppm) |
100
|
100
|
100
|
Hazard
Ratio |
0.3
|
0.9
|
1.5
|
PPE
Required |
No
|
No
|
Yes
|
Once
the need to use PPE has been established, the next step is to select
the proper type of PPE. PPE is rated by protection factors and each
PPE manufacturer has approved products at various protection factor
ratings. Generally, a half-mask respirator with particulate and
organic cartridges has a protection factor of 10X. Full-face respirators
with eye protection have protection factors to 50X, and supplied
breathing air systems have protection factors to 1000X. At a minimum,
the protection factor required for the PPE to be used must exceed
the highest Hazard Ratio.
In
situations where the PPE protection factor is many times higher
than the highest Hazard Ratio, painter exposure to solvent in the
recirculated booth may be lower than it would be without PPE and
recirculation. Also, some painters prefer the use of more comfortable,
battery-operated self-purging face masks (protection factor of 25X)
over half mask respirators when the lower protection factor is still
adequate for health and safety.
A health
and safety professional should be consulted with when setting up
any respiratory protection plan. This could be a large companys
corporate or plant level industrial hygienist. Smaller companies
can use a representative from an established supplier of PPE as
a resource. These professionals can help write the respiratory protection
plan, provide training and medical referrals if needed, document
fit testing and implement safeguards to assure PPE is always in
good working condition.
Questions
such as what is the permissible PEL, what is the actual exposure,
and what is the best PPE may seem complicated. The important point
is that there are scientific methods and OSHA procedures available
to answer all of these questions. When required, PPE can be combined
with properly designed fire safety features such as LEL interlocks
to provide a safe manned spray booth with recirculating exhaust.
As VOC pollution control becomes more widespread and applicable
to smaller VOC emission sources, one is likely to see more recirculated
manned spray booths.
Serving
the Finishing Industries. Since 1936.
PF Online and all contents are properties of Gardner Publications,
Inc.
All Rights Reserved.
|